Surge Testing of Electric Motor Windings

By John Johnson | 8 Nov 2026

Most winding failures start as weak insulation between turns. Resistance and insulation resistance tests do not stress that insulation. The surge test does.

What the test is for

A test equipment maker explains that the surge test is used to find shorts or insulation weaknesses in coils, windings, motors, generators, alternators and transformers. These faults are typically turn to turn, coil to coil or phase to phase. Shorts to ground can also be found, but insulation resistance and hipot tests identify them clearly. It also finds wrong connections and wrong turn counts. The maker says weak turn-to-turn insulation is the source of most winding failures, and that the surge test is the only test that can find weak insulation at elevated voltage.

How it works

A set of fast-rising pulses is passed through the coil or motor. The operator, or the standard, sets the voltage, which can range from the rms operating voltage of the motor to about 3.5 times it. The maker says a common value, recommended in the EASA AR100 standard, is two times the operating rms voltage plus 1000 V. The pulses produce a decaying wave in the circuit made up of the tester and the winding. The wave is compared with the wave from another coil or from the other phases. See the article on surge comparison for how to read the waves.

Where it is used

On individual coils, stators, wound rotors and fully assembled motors and generators, without turning the rotor, according to the maker.

Standards context

IEEE 522-2023 is a guide for testing turn insulation of form-wound stator coils. It covers individual coils after manufacture, coils in completely wound stators, coils and windings for rewinds, and windings in service as preventive maintenance. Typical machine ratings are 200 kW to 100 MW. The guide says its test voltage levels do not evaluate the ability of turn insulation to withstand abnormal surges, and that the repetitive spikes of variable frequency drives are not addressed. Use the standard that applies to your machine and keep to its voltages.

What a surge test will not find

The maker notes there are faults that only a surge test can find, such as weak turn insulation, and others that it does not find. Use it with winding resistance, insulation resistance and hipot tests. See motor winding resistance testing.

Practical cautions

  • The test is stressful. Use the voltage the standard sets and not more.
  • Do not apply a test voltage higher than the winding's rating allows.
  • Record the test voltage and the waves.

Frequently asked questions

What does a surge test find?

Turn-to-turn, coil-to-coil and phase-to-phase weaknesses, wrong turn counts and some connection errors.

What voltage is used?

It ranges from rated rms voltage up to about 3.5 times it. A common recommendation is two times rated plus 1000 V.

Does it replace a megohm test?

No. Shorts to ground are found by insulation resistance and hipot tests.

Which standard covers form-wound coils?

IEEE 522.

Does it cover VFD spikes?

IEEE 522 says repetitive VFD voltage spikes are not addressed.

Sources

  • Electrom Instruments: surge test values and diagnostics, surge comparison test pass/fail recommendations (manufacturer of test equipment)
  • IEEE SA: IEEE 522-2023 guide for testing turn insulation of form-wound stator coils (scope; VFD spikes not addressed)
  • EASA and AEMT study of motor repair impact on efficiency, ACEEE 2003 (burnout and stripping damage)