Motor Winding Connection: Star vs Delta

By Fang Deng | 3 Nov 2026

The star and delta connections are described in three-phase motor winding in star and delta. This article covers how they show up in the field: on nameplates, in terminal boxes and at starting.

What the nameplate says

A motor maker's guide lists standard voltage ranges by frame size. A motor for direct-on-line start or, with delta connection, also for star-delta start, may be marked, for instance, 380 to 415 V delta and 660 to 690 V star on a 50 Hz motor. The same winding is used on two supply voltages by changing the connection. The guide notes that the valid values vary by type, so check the product catalogue.

So a motor marked 400 V delta can be connected as delta on a 400 V supply, or in star on a supply that is higher by about the square root of three. In star, each winding sees the line voltage divided by the square root of three, and a starter supplier states that during star-delta starting the star connection reduces the voltage across each winding by this factor. Do not change a connection without the nameplate.

Star-delta starting

If the supply limits starting current, a star-delta starter can be used. Two manufacturers describe the same scheme. A motor wound for 400 V delta is started with the winding connected in star, which reduces the starting current to about 30 percent of the direct-on-line value and the starting torque to about 25 percent. After a time the windings are reconfigured in delta. A starter normally has three contactors, an overload relay and a timer.

Because of this, the motor must be delta connected during normal running to use the method.

Limits of star-delta starting

  • Light load only: a handbook says applications with load torque above 50 percent of rated torque cannot start this way, and the load must be low at the start, as with pumps and fans.
  • The switch-over can cause a high current and torque peak. In some cases the peak can be bigger than for a direct start.
  • Check that the reduced torque can accelerate the load over the speed range.

Checks in the terminal box

  1. Read the nameplate voltage and connection for your supply.
  2. Confirm the link positions match: three links for delta, the star point joined for star.
  3. Check winding resistance of each phase. See motor winding resistance testing.
  4. If using a star-delta starter, the winding ends have to be wired through the starter, which switches the connection.

Frequently asked questions

What does 400 V delta mean on a nameplate?

The winding is designed to be connected in delta on a 400 V supply.

Can I run a delta motor in star?

Only as the nameplate allows. In star each winding gets less voltage, so torque and output fall.

How much does star-delta starting reduce current?

About 30 percent of the direct-on-line current, and torque to about 25 percent, per two manufacturers.

Which connection is used for running with a star-delta starter?

Delta.

Does star-delta suit loaded starts?

No. It is for light-load starts.

Sources

  • ABB: low voltage motors guide (standard voltage ranges, direct-on-line and star-delta starting)
  • ABB: softstarter handbook (star-delta start, delta connection in normal run, starting current and torque)
  • Recon Electrical: star-delta starters working principles (voltage across each winding in star)