Motor Winding Connection: Star vs Delta
The star and delta connections are described in three-phase motor winding in star and delta. This article covers how they show up in the field: on nameplates, in terminal boxes and at starting.
What the nameplate says
A motor maker's guide lists standard voltage ranges by frame size. A motor for direct-on-line start or, with delta connection, also for star-delta start, may be marked, for instance, 380 to 415 V delta and 660 to 690 V star on a 50 Hz motor. The same winding is used on two supply voltages by changing the connection. The guide notes that the valid values vary by type, so check the product catalogue.
So a motor marked 400 V delta can be connected as delta on a 400 V supply, or in star on a supply that is higher by about the square root of three. In star, each winding sees the line voltage divided by the square root of three, and a starter supplier states that during star-delta starting the star connection reduces the voltage across each winding by this factor. Do not change a connection without the nameplate.
Star-delta starting
If the supply limits starting current, a star-delta starter can be used. Two manufacturers describe the same scheme. A motor wound for 400 V delta is started with the winding connected in star, which reduces the starting current to about 30 percent of the direct-on-line value and the starting torque to about 25 percent. After a time the windings are reconfigured in delta. A starter normally has three contactors, an overload relay and a timer.
Because of this, the motor must be delta connected during normal running to use the method.
Limits of star-delta starting
- Light load only: a handbook says applications with load torque above 50 percent of rated torque cannot start this way, and the load must be low at the start, as with pumps and fans.
- The switch-over can cause a high current and torque peak. In some cases the peak can be bigger than for a direct start.
- Check that the reduced torque can accelerate the load over the speed range.
Checks in the terminal box
- Read the nameplate voltage and connection for your supply.
- Confirm the link positions match: three links for delta, the star point joined for star.
- Check winding resistance of each phase. See motor winding resistance testing.
- If using a star-delta starter, the winding ends have to be wired through the starter, which switches the connection.
Frequently asked questions
What does 400 V delta mean on a nameplate?
The winding is designed to be connected in delta on a 400 V supply.
Can I run a delta motor in star?
Only as the nameplate allows. In star each winding gets less voltage, so torque and output fall.
How much does star-delta starting reduce current?
About 30 percent of the direct-on-line current, and torque to about 25 percent, per two manufacturers.
Which connection is used for running with a star-delta starter?
Delta.
Does star-delta suit loaded starts?
No. It is for light-load starts.
Sources
- ABB: low voltage motors guide (standard voltage ranges, direct-on-line and star-delta starting)
- ABB: softstarter handbook (star-delta start, delta connection in normal run, starting current and torque)
- Recon Electrical: star-delta starters working principles (voltage across each winding in star)