Partial Discharge in Motor Windings: Causes and Testing

By Vladimir Frolov | 6 Nov 2026

Partial discharge, or PD, is a local electrical breakdown in a small part of the insulation. It matters for high-voltage motors and generators, where the electrical stress in the insulation is high.

What it is

An ABB white paper calls PD a very small spark that occurs due to a high electrical field. In industrial high-voltage motors and generators the electrical stress can reach several kilovolts per millimetre, and discharge can occur inside the insulation, called internal PD, or on its surface, called external PD.

Causes

  • Internal PD generally occurs in microscopic air-filled voids that remain inside the insulation. The number and size of voids depend on the manufacturing procedures. Charge builds up around a void, and when the field across it exceeds the breakdown stress, a discharge short-circuits the void.
  • External PD occurs on the surface of the insulation when the local field exceeds the threshold to ionise air. Factors include poor air clearances, contamination on the end windings and variations or defects in the corona protection in the slots or on the end windings. A white powder deposit on the insulation is a visual sign.
  • A stator test paper lists problems that PD testing detects in form-wound stators: poor impregnation with epoxy, poorly made semiconductive coatings and insufficient spacing between coils in the end-winding area. It says PD testing detects most, but not all, of the common manufacturing and deterioration problems.

Why it damages insulation

The ABB paper says PD produces a short plasma burst and ultraviolet light, causes rapid local temperature spikes and creates chemically aggressive substances such as nitrogen oxides, ozone and nitric acid, so the insulation should be designed to withstand PD. See insulation systems for high-voltage motor windings for how the systems are built.

Testing

IEC 60034-27-1 covers off-line PD measurements on stator windings, meaning the winding is tested out of service. Its interpretation guidelines apply only to form-wound windings with conductive slot coating, usually machines of 6 kV and higher, at power frequency. For other windings the test procedures can be used for uniform manufacturing quality or for trending, including converter-driven machine windings.

Reading the results

  • The ABB paper says the magnitudes of individual PD measurements give little information, because they depend on sensors, settings, calibration, software and ambient humidity, temperature and noise, so results from different methods or equipment cannot be compared directly.
  • IEC 60034-27-1 says external factors affect the result, so PD measurements are comparable only under certain conditions.
  • In one ABB case, high PD was traced to loose coils in the slots of a 25-year-old motor that was not globally VPI treated. The coil movement, not the PD, would have eventually failed the motor.

PD is also a consideration for inverter-fed motors; see corona-resistant magnet wire.

Frequently asked questions

What is partial discharge?

A small spark in or on the insulation caused by a high local electric field.

Which motors are tested?

The sources cover high-voltage machines, for example 3.3 kV and above, and 6 kV and above for the IEC interpretation guidelines.

What is the difference between internal and external PD?

Internal PD happens in voids inside the insulation. External PD happens on the surface.

Can I compare PD numbers between testers?

Not directly. Magnitudes depend on equipment and conditions.

What does IEC 60034-27-1 cover?

Off-line PD measurements on stator windings.

Sources

  • ABB: controlling partial discharge in high voltage motors and generators (white paper; internal and external PD, effects, interpretation limits)
  • IRIS Power: objective methods to interpret partial-discharge data on rotating-machine stator windings (PD on machines of 3.3 kV and above, problems detected, false indications)
  • IEC 60034-27-1:2017 sample copy: off-line partial discharge measurements on stator windings (scope, comparability limits)
  • KTH: a literature review, the nature of partial discharges in stator insulation