Common Motor Winding Defects and Their Causes
A burned winding tells a story. Where the damage is and how it looks usually points to the cause. EASA publishes an illustrated guide to three-phase stator winding failures. This article summarises its causes in text.
Open supply: single-phasing
A single-phased winding, wye or delta connected, is the result of an open in one phase of the supply, usually a blown fuse, open contactor, broken power line or bad connection.
Thermal damage
- Phase damage due to unbalanced voltage: thermal deterioration in one phase from unequal voltage between phases, caused by unbalanced loads on the source, a poor connection at the motor terminal or a high resistance contact. EASA notes that a one percent voltage unbalance may give a six to ten percent current unbalance.
- Overload: thermal deterioration in all phases from load beyond the motor rating. EASA notes under-voltage and over-voltage outside NEMA limits produce the same deterioration.
- Locked rotor: severe thermal damage in all phases from very high current, which may also result from excessive starts or reversals.
Insulation faults
EASA gives the same typical causes for these failures: contaminants, abrasion, vibration or voltage surge.
- Shorted phase to phase.
- Shorted turn to turn.
- Shorted coil.
- Grounded at the edge of the slot, or in the slot.
- Shorted connection.
Voltage surge
Insulation failures from voltage surges are often the result of switching of power circuits, lightning strikes, capacitor discharges and solid-state power devices. See surge testing of electric motor windings for how a surge test checks turn insulation, and corona-resistant magnet wire for inverter-fed motors.
Defects added by repair
The EASA and AEMT study of rewinding found that process damage can raise losses: copper loss from lack of control of mean length of turn, stray loss from stripping damage, core loss from the burnout process and friction loss from over-greasing bearings. Burning out below 360 C may not break down the varnish and can lead to mechanical damage when coils are pulled, and burning out hotter than 360 C for organic core plate, or 400 C for inorganic, can damage the interlaminar insulation. See motor rewinding vs new motor winding.
Why the cause matters
Replacing a burned winding without finding the cause repeats the failure. A single-phased motor points to the supply, a fuse or contactor. Damage in all phases points to overload, locked rotor or excessive starts. Damage in one phase points to unbalanced voltage or a poor connection. Turn, coil and ground failures with no thermal pattern point to contaminants, abrasion, vibration or surge, according to EASA. The motor is often the victim, and the fix is on the supply or the load.
How to use this
- Photograph the winding before cleaning.
- Note which phases and coils are damaged.
- Match the pattern to the causes above.
- Check the supply, the load and the starts, not only the motor.
- Fix the cause before restarting a repaired motor.
Frequently asked questions
What causes single-phasing?
An open in one supply phase: blown fuse, open contactor, broken line or bad connection.
What does unbalanced voltage do?
It heats one phase. One percent voltage unbalance may give six to ten percent current unbalance.
What causes turn-to-turn shorts?
Contaminants, abrasion, vibration or voltage surge, according to EASA.
What does overload damage look like?
Thermal deterioration of the insulation in all phases.
Can a rewind add defects?
Yes, if burnout, stripping and winding are not controlled.
Sources
- EASA: failures in three-phase stator windings (single-phasing, overload, unbalance, locked rotor, surge, contaminants)
- EASA and AEMT study of motor repair impact on efficiency, ACEEE 2003 (burnout and stripping damage)